NameAir Handling Unit
Category23-33 25 00 : Air Handling Units
DescriptionAir Handling Unit_63300000 J
Installed ByContractor
ManufacturerVES Andover Ltd
ModelNumberMAX37/A/SW/S  (video search)
Reference23 06 70.13.A

5 items found
PropertyValueUnit
AHU Apparant Load1040VA
AHU Cooling Capacity56445488J
AHU Heating Capacity60665711J
Keynote23 06 70.13.An/a
Voltage230V

1 item found
NameAccess ThruInstalledOnSerial NumberBar Code
Air Handling Unit110502-06-2023T01:01:01EVCB173-1/FP-E/RT/G4/ISCn/a

11 items found
DocumentTypeStatusDescription
24V Open Close Damper MotorProduct DataApprovedProduct Data File Collection Form
Airflow Pressure Switch - FittedProduct DataApprovedProduct Data File Collection Form
ELGN1050 Motor Isolator Supplied Fitted & Pre-WiredProduct DataApprovedProduct Data File Collection Form
Filter Pressure Switch - FittedProduct DataApprovedProduct Data File Collection Form
Fitted & Pre-Wired Isolator To Suit 1 No. Damper MotorProduct DataApprovedProduct Data File Collection Form
InstructionsInstructionApprovedProduct Data File Collection Form
Magnehelic Gauge To Suit 0-250 PaProduct DataApprovedProduct Data File Collection Form
Mfg WarrantyCertificateApprovedProduct Data File Collection Form
O&M ManualOperations and MaintenanceApprovedProduct Data File Collection Form
Parts ListPartApprovedProduct Data File Collection Form
Product DataProduct DataApprovedProduct Data File Collection Form

Available
Mfg. Warranty Descriptionn/a
Mfg. Parts POCVES Andover Ltd
Mfg. Parts Duration1 year
Mfg. Labor POCVES Andover Ltd
Mfg. Labor Duration1 year

Extended Warranty POCn/a
Ext. Durationn/a

12 items found
PartDescriptionRcmd / CriticalSupplierPart No.
Damper MotorDescription(not identified)(supplier not found)PartNumber
Drive Belt220V-240V Open Close Damper Motor with Ext. Cable(not identified)VesDirectNM230
Bushingn/a(not identified)VesDirect1000QXPZ
Pulleyn/a(not identified)VesDirect1108-3/4
Fann/a(not identified)VesDirect100X2SPZ
Filter SetForward Curved Belt Driven Fan c/w FEET(not identified)VesDirectTLZ160F
Airflow SwitchWeathermaster Size 1 Filter Kit - Pack of 3(not identified)VesDirectWMDFKT100
ManometerAirflow Pressure Switch c/w Pitot probe & silicone tube(not identified)VesDirectAPS930/A
Air Quality SensorManometer c/w Probes(not identified)VesDirectM8/F
Controller TransformerAir Quality Sensor with Duct Sensor(not identified)VesDirectAQ2/D
ControllerSpeed Controller - Single Phase 9A Transformer(not identified)VesDirectTR8
CapacitorSpeed Controller(not identified)VesDirectVS2E

Frequency: 12 months
TaskDescriptionDuration
1For individual component maintenance requirements please refer to the relevant section of the manufacturers O&M Manual.0 minutes
2The belt drive should be thoroughly checked. If belts are found to be loose or worn, retighten or replace as necessary. Refer to relevant accompanying documentation for details and recommended tension.30 minutes
3Filters should be inspected regularly. If they are found to be heavily soiled or damaged they should be replaced immediately.30 minutes
4The general operation of the unit should be inspected, particularly for noise from bearings, motors and fans. An irregular noise could signify that unit failure is imminent.30 minutes
5Check for dust build-up in the system, especially around the impeller. Remove dust if necessary. Failure to do this periodically could lead to a loss of performance or cause the fan to become out of balance, ultimately leading to bearing failure.30 minutes
6Coils should be inspected to ascertain if any foreign matter has accumulated between the fins and that the coil connections are free from any leaks.30 minutes
7Should any matter be found, the coils should be cleaned using a soft brush and mild solution of commercial detergent. If heavily contaminated, a steam lance may be used.30 minutes
8Care should be taken so as not to damage or distort the fins during this cleaning process.30 minutes
9Periodically inspect heat exchange matrix for any debris, dust or dirt build up. Frequent contamination might be as a result of poor filtration and should be investigated.30 minutes
10Under NO circumstances should the heat exchanger be steam cleaned.30 minutes
11Ensure the drain pan and the drain connection is free from debris ensuring any condensate produced can freely drain away.30 minutes
12Max units are supplied with either unpainted galvanized sheet steel or powder coat paint finishes. Check all painted items to ensure that they have not deteriorated. Repaint as necessary. Paint can be supplied upon request. Checks should be carried out for missing fasteners.30 minutes

Frequency: 6 months
TaskDescriptionDuration
1For individual component maintenance requirements please refer to the relevant section of the manufacturers O&M Manual.0 minutes
2The belt drive should be thoroughly checked. If belts are found to be loose or worn, retighten or replace as necessary. Refer to relevant accompanying documentation for details and recommended tension.30 minutes
3Filters should be inspected regularly. If they are found to be heavily soiled or damaged they should be replaced immediately.30 minutes
4The general operation of the unit should be inspected, particularly for noise from bearings, motors and fans. An irregular noise could signify that unit failure is imminent.30 minutes

Frequency: 6 months
TaskDescriptionDuration
1For individual component maintenance requirements please refer to the relevant section of the manufacturers O&M Manual.0 minutes
2The belt drive should be thoroughly checked. If belts are found to be loose or worn, retighten or replace as necessary. Refer to relevant accompanying documentation for details and recommended tension.30 minutes
3Filters should be inspected regularly. If they are found to be heavily soiled or damaged they should be replaced immediately.30 minutes
4The general operation of the unit should be inspected, particularly for noise from bearings, motors and fans. An irregular noise could signify that unit failure is imminent.30 minutes
5Check for dust build-up in the system, especially around the impeller. Remove dust if necessary. Failure to do this periodically could lead to a loss of performance or cause the fan to become out of balance, ultimately leading to bearing failure.30 minutes
6Coils should be inspected to ascertain if any foreign matter has accumulated between the fins and that the coil connections are free from any leaks.30 minutes
7Should any matter be found, the coils should be cleaned using a soft brush and mild solution of commercial detergent. If heavily contaminated, a steam lance may be used.30 minutes
8Care should be taken so as not to damage or distort the fins during this cleaning process.30 minutes
9Periodically inspect heat exchange matrix for any debris, dust or dirt build up. Frequent contamination might be as a result of poor filtration and should be investigated.30 minutes
10Under NO circumstances should the heat exchanger be steam cleaned.30 minutes
11Ensure the drain pan and the drain connection is free from debris ensuring any condensate produced can freely drain away.30 minutes